TurboNet DASH 1 along with our integral HMI (Human Machine Interface) provides you a top notch control system. By using only the best, most effective hardware components, we guarantee results, whether we are making a smooth transition from your existing control system or installing a new one. With years of research and development, this system is now being offered to our customers. And with total customization, the possibilities are endless. Give us a call for a free demonstration.
Features
Celeron processors
Customized circuits and overspeed boards with individual fuses
Up to four monitors per HMI
Termination boards for each I/O module and each type
Color coordinated desk unit, rack mount HMI and EWS
Keyboardless operation with ergonomic trackball or mouse
Single, double and triple redundant I/O field interface options
Hot plug I/O modules online for non-vital signals
Click images below to enlarge.
Control Processors
Celeron 500MHZ control processors
128MB RAM
Primary and hot standby processor
Redundant power supplies available
Off the shelf hardware
Custom TurboNet chassis
Controller Cabinet
Houses control processors
Houses termination boards
Houses I/O modules
Houses power supplies
Separate expansion termination
cabinets available
Built in cabinet cooling fans
HMI Desk Unit
19” rack mounted HMI processors
Clean uncluttered desktop
External keyboard if desired (not required)
Ergonomic trackball or mouse
File drawer under HMI processor or historian processor
Power Supply
Redundant 300W
Gated Lambda 24 VDC power supplies
85-265 VAC or 120 to 330 VDC
Custom TurboNet chassis
Trouble shooting test points
Single or dual power sources
HMI Processor
Industrial computer chassis
Power, fan, temp, hard drive, power supply
status lights
Redundant power supplies available
Celeron 850MHZ
128MB RAM
Monitors
One to four monitors per HMI processor
Standard IS color LCD flat screen (two)
Unlimited size or type available
Ergonomic and compact design
17” dual monitor standard offering
View up to four screens at each HMI
Termination Boards
Clean organized internal wiring
Standard interconnection cables
Berg jumper options
Circuit protection
Power connection source jumper
One board per each I/O module type
Organized field termination
Inputs and outputs individually fused
Termination boards for each standard and
custom I/O module
Overspeed Module/Board
Three I/O modules for three speed input
I/O module processing for back up overspeed
protection
I/O modules pass digital speed signal to EIOa
data highway
Three overspeed boards hardwired in 2 out of
3 trip logic
Control processors provide primary overspeed
protection
Enough sensitivity to read turning gear speed with
passive pickups
Servo Control Module and Termination Board
Open loop and closed loop control
Single, redundant and triple redundant servo coil
and LVDT interface options
Unlimited size or type available
Termination board Berg jumper configuration
Open loop 0-200 MA output available
Onboard processor in servo I/O module
LVDT position controlled pilot valve servo
loop supported
200HZ scan rate
Mag pickup input for gas turbine fuel control
Vibration Module and Termination Board
(not pictured)
Real time vibration signal analysis
For displacement (prox probes) and velocity
(seismic probes)
Power supply available to power proximeters
Onboard processor in custom I/O module for
signal evaluation
1x filtered magnitude and angle placed on data highway
2x filtered magnitude and angle placed on data highway
Unfiltered magnitude placed on data highway
Gap voltage (shaft position) placed on data highway